Telehouse Moscow
About Telehouse Moscow
Telehouse Moscow is the first Russian Data Center to be provided and managed by a globally trusted brand. It is strategically located in the center of the capital, within a 66,736 sq. ft colocation facility, the only Tier III design and facility certified site of its kind in Eastern Europe. A carrier neutral Data Center with a meet-me-room and connected to the M9/M10, Telehouse Moscow is well positioned to ensure your business can grow within this now accessible emerging market.
Multinational corporations will be able to deploy Telehouse Moscow as a primary or secondary site for business-critical applications with access to multilingual remote hands staff and guarded by highly impressive security levels making it the most secure commercial Data Center in Russia.
Data Center Specifications
Power:
- Standard power to rack at 4.5kW
- 8.5 MW total power to building
- 6 x 6kV incoming power
- 6 independent transformers
- 6 fully automated generators (N+1)
- 6 fuel tanks (84 hrs)
- 6 redundant UPS supplies (N+1)
- 10 min battery back-up time per module
- LV N 1, A&B each data hall 400V via
dual busbar system - Design target: 1.5 PUE rating at full load
Environment & Air Conditioning:
- 5.4 MW cooling
- Room cooling units design: Chilled Water Type (N+1)
- 8 Chillers + 8 DACs cooling technology
- 5 CRAC units per hall (N+1)
- Hot/Cold aisle containment
- Operating conditions maintained at: chillers -31°F to +95°F, dry coolers -31°F to +50°F
Connectivity:
- Carrier neutral facility offering customers freedom of choice
- Access to key network operators including Orange, Mastertel, Beeline, Megafon and KDDI
- Access to a number of communication service providers enabling clients to connect to any Data Center in Moscow, as well as to M9 and M10 providing access to over 300 telecom providers
- 2 dedicated 3.94 inch conduits from MMR to each data hall
- Meet-me-room onsite with 20 carrier spaces
Fire Detection & Suppression:
- VESDA (Very Early Smoke Detection System)
- Fully monitored automated detection and fire alarming system
- NOVEC 1230, under floor and overhead fire suppression
- Fire rating – 2 hour rated walls, ceilings, floors
Security Systems:
- Central alarm monitoring with optional rack monitoring service
- 9 foot security fence
- Barrier controlled car access
- The building is covered by 120 cameras in total mounted to provide 360° view
- All corridors, access doors and other critical areas are covered by CCTV cameras with motion detection and DVR recording kept for a minimum of 3 years
- Minimum six 24/7 onsite security staff
- Entry to critical equipment areas including security station, control center and corridors is controlled by a combination of access card reader and IRIS scanner systems
- All data halls are controlled by access card reader and biometric hand scanner
- Single point of entry system with mantraps
Additional Specifications:
- Steel framed building construction
- 20.89 lbf/sq. ft raised floor design load
- Water leak detection system
Additional Services:
- 23,680 sq. ft offices for Disaster Recovery/IT staff
- 24/7 remote hands services
- KDDI manage all on-site connectivity, managed services and technical support with multilingual staff